Elicit: Comparative Energy Efficiencies of Renewable Sources for AI Data Centers

Skip to main content

Comparative Energy Efficiencies of Renewable Sources for AI Data Centers

Research reportView only

Create alertChat

February 28, 2025

What are the comparative energy efficiencies of renewable energy sources for powering large-scale artificial intelligence and machine learning data centers?

Wind, solar, and hybrid renewable systems show high efficiency rates between 90-96% for AI data centers, with solar offering potential grid independence and hybrid systems providing balanced performance.

Abstract

Renewable energy sources yield efficiency benefits in data centers across diverse implementations. Wind‐driven systems report usage and efficiency figures as high as 94–96% (Li et al., 2012) and energy savings of 20–30% (Adnan and Gupta, 2014), while solar‐based approaches can eliminate grid dependency in some configurations—up to 100% grid energy reduction with a 75% decrease in overall electricity costs (Goiri et al., 2013). In facilities dedicated to artificial intelligence workloads, one study notes a 12.5% reduction in energy consumption (Ajagekar and You, 2024). Distributed data centers that employ hybrid systems combining wind and solar have achieved renewable energy usage of 90.8% along with energy cost reductions near 15.3% (Liu et al., 2024), and integrated strategies report cost cuts up to 58% paired with marked carbon emission declines (Mohsin et al., 2024).

Other studies report comparable enhancements through load balancing and real‐time scheduling—with renewable energy penetration gains between 40% and 60% (Krioukov et al., 2011)—and advanced storage integration that further stabilizes performance. Taken together, the findings show that, when properly managed, wind, solar, and hybrid renewable energy systems can offer high energy utilization and efficiency in large-scale data centers supporting AI and machine learning workloads.

Methods

We analyzed 25 sources from an initial pool of 500, using 8 screening criteria. Each paper was reviewed for 5 key aspects that mattered most to the research question. More on methods

Papers identified with Elicit search

n = 500

Papers screened using: AI/ML Data Center Focus, Renewable Energy Analysis, Energy Efficiency Metrics, Empirical Evidence, Economic Data, Energy Source Focus, Empirical Validation, Measurement Detail

n = 500

Papers screened out

n = 475

Papers included for extraction

n = 25

Press enter or space to select a node.You can then use the arrow keys to move the node around. Press delete to remove it and escape to cancel.

Press enter or space to select an edge. You can then press delete to remove it or escape to cancel.

Paper search

Using your research question “What are the comparative energy efficiencies of renewable energy sources for powering large-scale artificial intelligence and machine learning data centers?”, we searched across over 126 million academic papers from the Semantic Scholar corpus. We retrieved the 500 papers most relevant to the query.

Screening

We screened in sources based on their abstracts that met these criteria:

We considered all screening questions together and made a holistic judgement about whether to screen in each paper.

Data extraction

We asked a large language model to extract each data column below from each paper. We gave the model the extraction instructions shown below for each column.

Describe the primary research methodology used in the study. Specify the type of analysis (e.g., simulation, empirical study, modeling, case study).

Look for details in the methods section. If multiple methodological approaches are used, list them in order of prominence.

Examples of acceptable responses:

If methodology is unclear, write “Unable to determine” and note the page or section where methodology is discussed.

Identify the specific data sources, computational traces, or datasets used in the study.

Locate this information in the methods or data section. Provide specific details such as:

If multiple data sources are used, list all in order of significance. If no specific data sources are mentioned, write “Not specified”.

Describe the specific approach used to integrate or optimize renewable energy in data center operations.

Look in the methods, results, and discussion sections. Capture key strategies such as:

Provide specific quantitative details if available (e.g., “40-60% improved renewable energy penetration”).

If no clear integration approach is identified, write “No specific approach described”.

Identify and extract the specific metrics used to measure energy efficiency or renewable energy utilization.

Search the results and methods sections for:

Record the exact metric, numerical value, and units. If multiple metrics are used, list all.

If no quantitative metrics are provided, write “No specific metrics reported”.

Extract the main findings related to renewable energy use in data centers.

Look in the results, discussion, and conclusion sections. Focus on:

Aim for a concise summary (2-3 sentences) that captures the core research conclusion.

If no clear findings are identifiable, write “No substantive findings reported”.

Results

Characteristics of Included Studies

Study

Study Type

Scale of Implementation

Geographic Region

Primary Energy Sources

Full text retrieved

Adnan and Gupta, 2014

Linear programming with simulation

Data center

No mention found

Wind, Solar

Yes

Ajagekar and You, 2024

Robust optimization with modeling

Artificial Intelligence (AI) data centers

United States

No mention found

No

Fridgen et al., 2021

Analytical modeling with empirical analysis

Data center

Germany

Wind

Yes

Goiri et al., 2013

Empirical analysis with prototype

Small-scale data center

No mention found

Solar

Yes

Hernández, 2017

Simulation-based design

Mid-sized data center

Netherlands, Europe

Solar, Wind, Biomass

No

Kang and Youn, 2019

Model predictive control with empirical analysis

Graphics Processing Unit (GPU)-based clusters

No mention found

No mention found

No

Kang et al., 2019

Deep learning with empirical analysis

Distributed data centers

United States

No mention found

No

Khanmohammadi et al., 2022

Data modeling and AI simulation

Geothermal energy system

No mention found

Geothermal

No

Kim et al., 2016

Stochastic optimization with modeling

Power grid scale

No mention found

Wind

No

Krioukov et al., 2011

Simulation

Internet data centers

No mention found

Wind

No

toof

Pageof

View 15 more rows

Analysis of the included studies reveals:

Study Types:

Scales of Implementation:

Geographic Regions:

Primary Energy Sources:

Many studies investigated multiple energy sources, particularly combinations of wind and solar power. The research spans various scales, from individual data centers to large-scale distributed systems, with a notable focus on the United States. Simulation and modeling techniques were predominant in the methodologies employed.

Energy Efficiency Analysis

Comparative Performance Metrics

Study

Energy Source

Efficiency Rating

Cost per MWh

Carbon Impact

Adnan and Gupta, 2014

Wind, Solar

20-30% energy savings

No mention found

No mention found

Ajagekar and You, 2024

No mention found

12.5% energy consumption reduction

No mention found

9.8% carbon emissions reduction

Fridgen et al., 2021

Wind

73% renewable energy usage

No mention found

No mention found

Goiri et al., 2013

Solar

Up to 100% grid energy reduction

75% overall grid electricity cost reduction

No mention found

Hernández, 2017

Solar, Wind, Biomass

2-81% renewable energy coverage

No mention found

No mention found

Kang and Youn, 2019

No mention found

No mention found

No mention found

No mention found

Kang et al., 2019

No mention found

No mention found

25% energy cost reduction

No mention found

Khanmohammadi et al., 2022

Geothermal

First law efficiency: 0.3322

No mention found

No mention found

Kim et al., 2016

Wind

No mention found

No mention found

No mention found

Krioukov et al., 2011

Wind

40-60% better renewable energy penetration

No mention found

No mention found

toof

Pageof

View 15 more rows

Analysis of the comparative performance metrics reveals:

Energy Sources:

Efficiency Ratings:

Cost per MWh:

Carbon Impact:

Geographic and Temporal Variations

Several studies highlight the importance of geographic and temporal variations in renewable energy integration for data centers:

Implementation Patterns

Hybrid Systems Performance

Several studies report on the performance of hybrid renewable energy systems in data centers:

Load Balancing Strategies

Several studies highlight the importance of load balancing strategies for optimizing renewable energy utilization in data centers:

Storage Integration

Several studies highlight the importance of energy storage systems in maximizing the effectiveness of renewable energy sources in data centers:

Operational Considerations

Cost-Effectiveness

The studies report varying degrees of economic benefits from integrating renewable energy sources into data center operations:

System Reliability

Several studies propose strategies to enhancesystem reliability in renewable-powered data centers:

  1. Hybrid Energy Systems:
    • Li et al. (2016) demonstrated that their GreenWorks framework, which manages hybrid renewable energy systems, can achieve near-optimal workload performance while maintaining carbon-neutral operations.
  2. Energy Storage Integration:
    • Liu et al. (2011) highlighted the importance of small-scale storage, particularly when combined with geographical load balancing.
  3. Advanced Scheduling Algorithms:
    • Krioukov et al. (2011) showed that supply-following job schedulers can improve renewable energy penetration by 40-60%.
  4. Predictive Models:
    • Park and Kang (2024) used a Gated Recurrent Unit (GRU)-based predictor to forecast renewable energy generation, which informs their RA-FS approach. This method improves renewable energy utilization by 31%.
  5. Reinforcement Learning:
    • Wang et al. (2021) employed a multi-agent reinforcement learning (MARL) method that increases Service Level Objective (SLO) satisfaction by up to 35%.
  6. Geographical Distribution:
    • Liu et al. (2011) emphasized the benefits of geographical load balancing in reducing the required capacity of renewable energy.
  7. Innovative Energy Solutions:
    • Temiz and Dincer (2022) showcased a solar-driven hydrogen energy system that achieves 100% self-sufficiency in Arctic regions.

Scaling Implications

As data centers continue to grow in size and energy demand, particularly with the increasing prevalence of AI and ML workloads, several studies offer insights into how renewable energy solutions can be scaled:

  1. Geographical Scaling:
    • Liu et al. (2011) emphasized the importance of geographical load balancing in reducing the required capacity of renewable energy.
  2. Hybrid Systems at Scale:
    • Li et al. (2016) demonstrated that their GreenWorks framework for managing hybrid renewable energy systems becomes more efficient with deeper renewable power penetration.
  3. Large-Scale Optimization:
    • Liu et al. (2024) showed that their ECMR algorithm can achieve high renewable energy utilization (90.8%) even when applied to multiple data center locations.
  4. Scalable Load Balancing:
    • Krioukov et al. (2011) proposed supply-following load adjustment strategies that can improve renewable energy penetration by 40-60%.
  5. Infrastructure Considerations:
    • Patterson et al. (2021) highlighted that strategic choices in data center location and infrastructure can lead to significant reductions in carbon footprint, potentially up to 100-1000X.
  6. AI-Driven Management:
    • Several studies, including Wang et al. (2021) and Shen et al. (2023), use AI and machine learning techniques to optimize renewable energy integration.

References

G. Fridgen, Marc Körner, Steffen Walters, Martin Weibelzahl\ (2021).Not All Doom and Gloom: How Energy-Intensive and Temporally Flexible Data Center Applications May Actually Promote Renewable Energy Sources. Business & Information Systems Engineering

Zhenhua Liu, Minghong Lin, A. Wierman, S. Low, L. Andrew\ (2011).Geographical load balancing with renewables. PERV

Íñigo Goiri, William A. Katsak, Kien Le, Thu D. Nguyen, R. Bianchini\ (2013).Parasol and GreenSwitch: managing datacenters powered by renewable energy. International Conference on Architectural Support for Programming Languages and Operating Systems

David A. Patterson, Joseph Gonzalez, Quoc V. Le, Chen Liang, Lluís-Miquel Munguía, and 4 more\ (2021).Carbon Emissions and Large Neural Network Training. arXiv.org

Chao Li, Rui Wang, D. Qian, Tao Li\ (2016).Managing Server Clusters on Renewable Energy Mix. TAAS

A. Krioukov, C. Goebel, S. Alspaugh, Yanpei Chen, D. Culler, and 1 more\ (2011).Integrating Renewable Energy Using Data Analytics Systems: Challenges and Opportunities. IEEE Data Engineering Bulletin

Kibaek Kim, Fan Yang, V. Zavala, A. Chien\ (2016).Data Centers as Dispatchable Loads to Harness Stranded Power. IEEE Transactions on Sustainable Energy

H. Shoukourian, D. Kranzlmüller\ (2020).Forecasting power-efficiency related key performance indicators for modern data centers using LSTMs. Future generations computer systems

Chenhan Xu, Kun Wang, Peng Li, Rui Xia, Song Guo, and 1 more\ (2020).Renewable Energy-Aware Big Data Analytics in Geo-Distributed Data Centers with Reinforcement Learning. IEEE Transactions on Network Science and Engineering

Chao Li, Amer Qouneh, Tao Li\ (2012).iSwitch: Coordinating and optimizing renewable energy powered server clusters. International Symposium on Computer Architecture

Mert Temiz, I. Dincer\ (2022).A Unique Bifacial PV and Hydrogen-Based Cleaner Energy System with Heat Recovery for Data Centers. Applied Thermal Engineering

Haoyu Wang, Haiying Shen, Jiechao Gao, Kevin Zheng, Xiaoying Li\ (2021).Multi-Agent Reinforcement Learning based Distributed Renewable Energy Matching for Datacenters. International Conference on Parallel Processing

Akshay Ajagekar, Fengqi You\ (2024).Variational Quantum Circuit Learning-Enabled Robust Optimization for AI Data Center Energy Control and Decarbonization. Advances in Applied Energy

S. Khanmohammadi, F. Musharavati, Rasikh Tariq\ (2022).A framework of data modeling and artificial intelligence for environmental-friendly energy system: application of Kalina cycle improved with fuel cell and thermoelectric module. Chemical engineering research & design

Matthew McMullen, A. Wemhoff\ (2024).Data Center Environmental Burden Reduction Through On-Site Renewable Power Generation. ASME Journal of Engineering for Sustainable Buildings and Cities

Longjun Liu, Hongbin Sun, Chao Li, Yang Hu, Nanning Zheng, and 1 more\ (2016).Towards an Adaptive Multi-Power-Source Datacenter. International Conference on Supercomputing

Lei Liu, Zicong Miao, Haijing Nan, Weize Li, Xiaodong Pan, and 4 more\ (2024).Energy and Carbon-aware Distributed Machine Learning Tasks Scheduling Scheme for the Multi-Renewable Energy-based Edge-Cloud Continuum. Science and Technology for Energy Transition

Syed Muhammad Mohsin, Tahir Maqsood, S. Madani\ (2024).Towards Energy Efficient Cloud: A Green and Intelligent Migration of Traditional Energy Sources. Energies

Dong-Ki Kang, Eunju Yang, Chan-Hyun Youn\ (2019).Deep Learning-Based Sustainable Data Center Energy Cost Minimization With Temporal MACRO/MICRO Scale Management. IEEE Access

Muhammad Abdullah Adnan, Rajesh K. Gupta\ (2014).Workload Shaping to Mitigate Variability in Renewable Power Use by Data Centers. IEEE International Conference on Cloud Computing

Hyuk-Gyu Park, Dong-Ki Kang\ (2024).Renewable-Aware Frequency Scaling Approach for Energy-Efficient Deep Learning Clusters. Applied Sciences

Dong-Ki Kang, Chan-Hyun Youn\ (2019).Real-Time Control for Power Cost Efficient Deep Learning Processing With Renewable Generation. IEEE Access

Haiying Shen, Haoyu Wang, Jiechao Gao, R. Buyya\ (2023).An Instability-Resilient Renewable Energy Allocation System for a Cloud Datacenter. IEEE Transactions on Parallel and Distributed Systems

William Rollinson, A. Urquhart, Murray Thomson\ (2025).Technoeconomic Feasibility of Wind and Solar Generation for Off-Grid Hyperscale Data Centres. Energies

Alfredo Hernández\ (2017).Powering Data Centers with Renewable Energy : Simulation-based design of an on-site System for a TUe Case Study FINAL REPORT

Download BIBDownload RISDownload TXT

Report

Status

Gather sources

500 sources found

Details

Screen sources

25 sources included

Details

Extract data

125 data points extracted

Details

Generate report

Save PDF

BIBLaTeX, ZoteroRISZotero, MendeleyTXTAPA BibliographyPDFPDFDOCXMicrosoft Word

Chat

Got some follow-up questions?

Sign up or sign in to chat with this report.

Back

iSwitch: Coordinating and optimizing renewable energy powered server clusters

Chao Li, Amer Qouneh, Tao Li

International Symposium on Computer Architecture·

2012·

137 citations

SourceDOI

Plain textPDFFigures

Searching for PDF

Unable to find PDF from source

Back

Research Methodology

Trace-driven simulation using real-world data center and wind power traces

Data Sources and Computational Environment

- Wind power data traces from The Wind Integration Datasets of the National Renewable Energy Laboratory. - Server utilization traces converted using SPECPower results. - Real-world workload logs from an online repository. - Geographic scope includes various locations as detailed in Table 4.

Renewable Energy Integration Approach

iSwitch integrates renewable energy into data center operations through a supply-aware power management strategy that follows renewable power variations. It uses a cooperative optimization approach with lazy tracking on the supply side and demand smoothing on the load side, along with a hierarchical switching control scheme to dynamically allocate server loads. This approach achieves 94% renewable energy utilization and significantly reduces job waiting times and network traffic.

Energy Efficiency Metrics

- Renewable Energy Utilization (REU): 94% - Energy Efficiency: 96%

Primary Findings on Renewable Energy and Data Centers

iSwitch significantly reduces network traffic and job waiting times while maintaining 96% renewable energy utilization in data centers. It achieves a balance between renewable energy use and performance, offering substantial operational benefits with minimal cost increase.

Large-scale computing systems such as data centers are facing increasing pressure to cap their carbon footprint. Integrating emerging clean energy solutions into computer system design therefore gains great significance in the green computing era. While some pioneering work on tracking variable power budget show promising energy efficiency, they are not suitable for data centers due to lack of performance guarantee when renewable generation is low and fluctuant. In addition, our characterization of wind power behavior reveals that data centers designed to track the intermittent renewable power incur up to 4X performance loss due to inefficient and redundant load matching activities. As a result, mitigating operational overhead while still maintaining desired energy utilization becomes the most significant challenge in managing server clusters on intermittent renewable energy generation. In this paper we take a first step in digging into the operational overhead of renewable energy powered data center. We propose iSwitch, a lightweight server power management that follows renewable power variation characteristics, leverages existing system infrastructures, and applies supply/load cooperative scheme to mitigate the performance overhead. Comparing with state-of-the-art renewable energy driven system design, iSwitch could mitigate average network traffic by 75%, peak network traffic by 95%, and reduce 80% job waiting time while still maintaining 96% renewable energy utilization. We expect that our work can help computer architects make informed decisions on sustainable and high-performance system design.

1.Introduction

Today, cloud computing is redefining the IT infrastructure. Data centers have become essential to the operation of businesses, academic, and governmental institutions. Nevertheless, the power-provisioning problem is challenging data center designers, as the environmental impact of IT becomes a growing concern worldwide. It has been shown that worldwide data centers run the risk of doubling their energy consumption every 5 years [1]. In a recent report on the carbon impact of cloud computing, the environmental activist group Greenpeace called on data center operators to make renewable energy a priority as more data centers are being built to meet the cloud needs [2]. In addition, the government also imposes a "carbon tax" on energy-hungry IT companies while giving federal tax credit (e.g., 30% to the total cost) for using renewable energy.

Consequently, there has been an increasing push towards the vision of renewable energy powered sustainable computer system design.

In this study, we investigate an emerging data center design scheme that integrates on-site renewable energy sources into the data center infrastructure. Such a design scheme has recently drawn considerable attention as the IT industry is starting to assume responsibility for supporting long-term computing system sustainability. Internet giants, such as Google, Microsoft and Yahoo! all power part of their data centers using renewable energy resources. Using grid utilities as backup, many Web Hosting service providers power their data centers with on-site renewable energy sources as well [3, 4, 5, 6] . With those green computing initiatives, each data center is able to eliminate nearly 20,000 lbs or more carbon dioxide emission per year [3, 4] .

While many research efforts are focused on reducing idle server power [7], lowering provisioned power capacity [8], and optimizing power allocation [9,10,11], designing renewable energy powered data centers is still challenging and requires careful exploration. Due to the intermittent nature of renewable energy, existing designs typically use on-site renewable generation to compensate part of their total data center power requirement. When renewable energy contributes a large portion of the load power demand (e.g., > 15%), variations in renewable power supply have a significant impact on load operation [12]. Existing power management schemes miss the opportunity to harvest renewable generation since they typically assume a fixed and predictable power supply and cannot handle the power variation gracefully. Recent proposals leverage load tuning mechanisms (e.g. DVFS, CPU power states) to track the renewable power variation [13,14] but incur unnecessary load tuning activities. Over-tuning of the load power degrades system response time and provides very limited efficiency return.

Figure 1 shows the tradeoff we found between power tuning overhead and energy utilization. The evaluated system tracks the renewable power budget whenever renewable generation decreases (to avoid brownout); it tracks the power supply surge with a pre-defined coverage factor (CF). As shown in Figure 1 -a, compared to no-tracking (i.e., CF=0), always tracking the power variation (i.e., CF = 1) increases the load tuning overhead by 2X. Nevertheless, the range of energy utilization return is less than 15%, as shown in Figure 1 In this paper, we explore the design tradeoffs between energy utilization and load tuning overhead in renewable energy driven computing systems. We propose iSwitch, a power management scheme that maintains a desirable balance between renewable energy utilization and data center performance. The novelty of our design is two-fold. First, iSwitch is a supply-aware power management scheme. It applies the appropriate power management strategy for wind variation scenarios to achieve the best design tradeoff. Second, iSwitch has a built-in supply/load cooperative optimization mechanism that is able to minimize the performance degradation due to load power tuning overhead while still maintaining high renewable energy utilization and low cost. Although we describe our design in the context of wind power supply, it applies to a variety of intermittent renewable energy sources.

This paper makes the following contributions:  Design: We propose iSwitch control architecture, an application-independent hierarchical load tuning scheme that leverages load migration to best utilize the renewable energy generation.  Characterization: Our characterization of renewable power variability and data center load fluctuation reveals that power tracking can be done in a less frequent, light-weight manner. In this case, we can significantly reduce the load tuning overhead with negligible efficiency degradation.

 Optimization: We propose supply/load cooperative optimization that not only avoids redundant load tuning activities invoked by severe renewable power supply variation, but also minimizes unnecessary power control activities invoked by stochastic data center load fluctuation. Compared to the state-of-the-art renewable energy-driven designs, iSwitch could reduce job waiting time by 80%, mitigate average network traffic by 75%, and rush hour traffic by 95%. Moreover, iSwitch still maintains 96% of the energy efficiency.

The rest of this paper is organized as follows: Section 2 provides background and motivation. Section 3 characterizes wind power variation. Section 4 presents an overview of iSwitch and its control architecture. Section 5 introduces the two key constituents of iSwitch optimization. Section 6 describes our evaluation framework. Section 7 presents experimental results. Section 8 discusses related work and Section 9 concludes the paper.

2.Background and Motivation

Renewable energy supply (RES) is drawing growing attention in today's IT industry. In this section, we describe the motivations of renewable energy driven design and discuss why conventional solutions limit the development of sustainable IT.

2.1.Renewable Energy Driven Design

In spite of the intermittent nature of renewable energy sources, designing renewable energy powered data centers has many benefits beyond low carbon footprint. For instance, renewable power supplies are highly modular in that their capacity can be increased incrementally to match the gradual load growth [15,16]. This greatly reduces the over-provisioning loss of a data center since it takes a long time for the server load to catch up with the upgraded provisioning capacity. In addition, the latency between initiation and construction (a.k.a. construction lead-time) of renewable generation is significantly shorter than that of conventional power plants, reducing the financial and regulatory risks [15]. Moreover, the price and availability of renewable resources remain stable, simplifying long-term planning for IT companies [15, 17] .

2.2.Problem with Conventional Solutions

Conventionally, extra-scale battery farms can be used to regulate renewable power supply fluctuation. Such approach requires additional large capital investment and is not energy-efficient: the round-trip energy loss of batteries ranges between 5%~25% [18]. Furthermore, frequent charging and discharging the battery accelerates its aging and quickly wears it out [19]. This will further increase the environmental burden (i.e. recycling problem) and the downtime for maintenance.

Alternatively, feedback mechanisms such as net-metering [20] directly connects on-site renewable energy source to the local utility grid to gain high power provisioning availability. Nevertheless, net-metering is still in its infancy stage and aggressively relying on it can be hazardous to the utility operation. This is because grid operators are forced to switch their power stations frequently between operation and spinning standby modes to meet the unexpected feedback power surge. In addition, to ensure stability, the maximum renewable power penetration of the

Utilization

Coverage Factor transmission line also has a limit [15]. In the foreseeable future, these problems can be a major hurdle for going green.

Waiting for the grid to be "smart" will unnecessarily delay the long-term goal of sustainable IT. The motivation of this work is that the IT facility itself can be an enabler of sustainability and efficiency. Instead of adding additional power provisioning units and server clusters, our technique leverages existing data center infrastructure and load migration mechanisms to manage the time-varying renewable power. As an alternative to entirely relying on power grid or energy storage, we exploit intelligent data center self-tuning to manage the IT power provisioning. By reducing the dependence on large-scale batteries and utility power grids, our design improves data center sustainability with low cost while providing the operators with more active control of their server clusters.

3.Implications of Wind Power Variability and Intermittency

While the importance of managing renewable energy intermittency is recognized by recent studies [13,14], characterizing power variation behavior is still an unexplored area in the context of data center design. In this study we primarily focus on wind power variation since wind energy is cheaper and is also the most widely used renewable power technique for large scale facilities [15]. In this section, we first discuss wind power characteristics. We then demonstrate three critical power management problems in wind energy driven data centers and the associated optimization opportunities.

3.1.Wind Power Characteristics

A wind turbine generates electrical power by extracting kinetic energy from the air flow. While operating, the turbine converts wind energy to mechanical power through a rotor with multiple blades. Figure 2 shows the output characteristics of a GE wind turbine, whose power curve is divided into three regions by the designated operating wind speeds. The cut-in speed is the minimum speed at which the rotor and blade starts to rotate. The cut-off speed is the wind speed at which the turbine ceases its generation and shuts down for protecting the blade assembly.

In Figure 2 , we refer to the three regions as intermittent power outage period (Region-I), variable power generation period (Region-II) and stable power generation period (Region-III), respectively. In Region-I, wind power is intermittently unavailable because the wind speed is either too low or too high. In Region-II, the mechanical power delivered to the turbine generator is given by 3 0.5 p Av C   [15], where  is the air density, A is the swept area of the blades, v is the wind speed and C is called power coefficient factor. In Region-III, the wind turbine operates at its designated rated power.

Wind power has the highest variability in Region-II. To understand this, we show the probability distribution of wind speed in Figure 3 . The variations in wind speed are typically described by the Weibull distribution [15]:

In Equation-1, k is the shape parameter, c is the scale parameter and v is the wind speed. At most wind farm sites, the wind speed has the Weibull distribution with k = 2, which is specifically known as the Rayleigh distribution [15]. As shown in Figure 3 , the Rayleigh distribution function in Region-II is not monotonic. In this region, wind speed has equally high possibilities at a wide range of values. As a result, the wind turbine is more likely to incur time-varying wind speed in Region-II. In addition, the wind turbine output is a steep curve due to the cubic relation between wind power and wind speed. In this case, a small change of the wind speed can lead to large wind generation fluctuation. Therefore, the renewable power variability is typically significant in Region-II.

3.2.Power Management Regions

Figure 4 shows real traces of wind power supply and data center power demand. It illustrates the aforementioned three power generation scenarios, namely, intermittent wind power outage period (Region-I), low renewable generation with frequent fluctuation (Region-II), and full renewable generation with relatively stable output (Region-III). Similar region partition method is also applicable for intermittent renewable energy sources such as solar power and tidal power. In the following paragraphs we will discuss data center design considerations for each region.

Region-I: tune wisely. During the low generation period (i.e. Region-I), it is wise to shift data center load from renewable energy supply side to utility power. To tune the load power footprint, existing practices either put servers into low power states or apply power cycling techniques [14] on the hardware. Although these approaches show impressive power control capability, they sacrifice the computing throughput. In addition, it typically takes a long time (about tens of minutes as we observed) for the renewable energy generation to resume. As a result, for mission-critical systems, putting servers into sleep state and waiting for the renewable energy to resume is not wise, especially for those parallel computing machines with inter-node workload dependency.

Region-II: track wisely. Whenever the load power fluctuates or renewable energy generation varies, load matching is performed as a common practice to handle the power discrepancy [13,14]. In Region-II, the wind generation oscillates severely. The load power tuning is largely a result of the power supply variation, as shown in Figure 4 . However, aggressively matching the load to the supply results in little energy benefits but disturbs the normal server operation and degrades the performance of parallel workload. Therefore, seeking appropriate tracking timing becomes especially important. Region-III: schedule wisely. When the renewable energy is relatively stable, frequent load fluctuation contributes to a number of load tuning operations. In Figure 4 (Phase III), although the data center power has a relatively small dynamic range, frequent variation invokes a large number of back-and-forth load migration operations. Those tuning activities have little contribution to the overall renewable energy utilization but increase network traffic significantly. A well designed job scheduling that mitigates load power fluctuation will help lower the overhead.

We believe a renewable energy powered data center will frequently experience the aforementioned three power management regions throughout its lifetime. To improve overall quality of service, the best design practice should put the above scenarios together and provide a cooperative power management scheme.

4.An Overview of iSwitch Architecture

In this section we propose iSwitch, a holistic data center coordination and optimization scheme that ensures high renewable energy utilization and low operational overhead. As shown in Figure 5 , iSwitch is designed to provide autonomic load power balancing between conventional utility grid and renewable energy generation.

In Figure 5 , the on-site renewable power supply provides the data center with clean energy through a separate power line. We choose not to synchronize renewable power to the grid because the fluctuating nature of renewable energy often challenges the grid stability [21]. On the other hand, although one can leverage dual-corded servers to utilize two power supplies simultaneously, it is not energy-efficient when the computing load is low [22]. In this study, iSwitch explores computing load migration as an alternative of energy source integration.

4.1.Switching Mechanism

The basic idea behind iSwitch is switching, or the operation of performing a switch. In this study, the switch is defined as a load migration event that leads to redistribution of load power between different power supplies.

As an alternative to load power throttling, iSwitch intelligently shifts the computing load from one energy source to another to achieve best load power matching. We use virtual machine (VM) live migration to implement iSwitch since it is the most convenient way to perform load power shifting in a virtualized computing environment. Existing virtual machine power metering [23] also eases the monitoring and coordination of each individual VM.

Note that in Figure 5 , iSwitch does not require increasing the number of servers to meet the workload surge. In emergency scenarios, we use backup energy storage to temporarily support the load. According to Fan et al. [24], server clusters can spend more than 80% of the time within 80% of their peak power, and 98% of the time within 90% of their peak power. Therefore, the chance of workload triggered emergency is small. In this study, we assume that the number of renewable energy powered servers is less than 40% of the overall deployed machines since a data center typically consumes about 60% of its actual peak power [24]. In this case, even if the wind power is extremely low, the utility grid can still take over most of the load.

4.2.Control Mechanism

To handle the time-varying, intermittent renewable power, iSwitch dynamically allocates and de-allocates (i.e., "switches") the renewable energy powered server load. The supply/load variability makes the switch tuning challenging since the control should 1) globally respect the time-varying renewable budget and 2) locally avoid any power failure induced by load fluctuation. To this end, iSwitch uses a hierarchical switching control scheme, which can be easily incorporated into existing hierarchical power management methods such as [25].

Facility level: Figure 6 shows a global view of iSwitch control mechanism. The switching operation is controlled by a central switch controller (CSC), which communicates with a central power controller (a typical facility-level data center power controller), a switch scheduler and multiple cluster level switch controllers. CSC performs switch tuning based on the discrepancy between the load power consumption and the RES budget. Whenever needed, switching operations are scheduled by the switch scheduler, which stores profiling information for each server load and optimizes switching using load history records.

Cluster level: The switching allocation is assigned to local computing nodes via cluster-level switching controllers, which are counterparts to PDU-level power controllers. The cluster-level switching controller collects switching outcomes (i.e., the number of switching operations accomplished/failed) of each local computing node and feeds the information to the CSC for switching scheduler updates. The cluster-level controller improves the manageability of dynamic switching and reduces the overhead of CSC communication traffic.

Rack level: As shown in Figure 7 , a rack-level switch controller executes power supply switching and sends the execution outcomes to the CSC via a cluster-level switch controller. It also interacts with the rack-level power controller throughout the switching process to avoid any brownout. For example, whenever the power consumption of a server rack reaches its local renewable power budget, the power controller will signal the rack-level switch controller to throttle the switching activities. In addition, the rack-level power controller is able to perform power capping by manipulating the voltage and frequency modulator of the server. This will prevent over-loading if power switching cannot handle the load surge in time.

5.Optimizing Load Tuning Activities

This section proposes the supply/load cooperative optimization scheme of iSwitch. Our technique features a lazy tracking scheme on the supply side and a power demand smoothing scheme on the load side. This cooperative optimization is readily supported by existing data center architectures and is orthogonal to other system-level control and workload optimizations.

The switching scheduler is the key architecture for iSwitch, as shown in Figure 8 . It monitors the power provisioning status (i.e. powered by renewable energy or utility grid) of each server load (i.e., VMs). All the running loads within each cluster are indexed consecutively in a switch allocation buffer (SAB). A switching history table is used to store the switching frequency for each load. An optimizer computes the optimal switching assignment and a tracking module initiates the switching process.

To make load tuning decisions, iSwitch scheduler needs profiling information such as server utilization data from the load history table. The central power controller invokes scheduling activities in response to variations in renewable power supply and load power demand. Whenever necessary, the scheduler sends a sequence of load switching commands to the central switch controller for execution.

Load History Records

Central Switch Controller R U ...

Optimizer

Cluster ID Switch Allocation Buffer (SAB)

Tracking Module

Utility-Driven Server RES-Driven Server Shutdown

5.1.Lazy Power Supply Tracking

The first idea of iSwitch is to avoid tracking the severely fluctuant renewable power in Region-II (detailed in Section 3). Inside the scheduler, a tracking module manages iSwitch power tracking, as shown in Figure 8 . We call it lazy tracking because the module only harvests the relatively stable renewable energy generation. Note that iSwitch carefully distributes the switching activities across all the loads evenly to avoid local traffic jam. Lazy tracking: At each fine-grained interval, when switching is triggered by the CSC, an estimated switching assignment will be sent to the scheduler for calculating the switch operation balance (e.g., estimated assignment minus the baseline). If the switch balance indicates a reduced number of servers to RES connection, the scheduler signals the CSC to schedule the estimated assignment to avoid brownout. On the other hand, if the switching balance suggests an increased number of servers to RES connection (e.g., due to temporally decreased load or increased supply), the scheduler will signal CSC only if the balance is larger than a preset threshold (e.g., 10% of the baseline). In this case, we ignore the high-frequency switching surge which brings little benefit on renewable energy utilization but leads to excessive unnecessary load migration.

LRU distribution: Within each cluster, iSwitch allocates switch operations with least recently used (LRU) method, which avoids aggressively tuning a small set of computing nodes. Note that a naive switching allocation can result in unbalanced switching allocation. In Figure 9 we show the switching distribution as a result of round-robin scheduling. The average switching frequency is 200 times per day per VM. A small group of VMs receives up to 400 times per day. As a result, some racks may incur more performance penalty due to high communication traffic.

To implement LRU, iSwitch uses the switch frequency record stored in the switching history table. The operation of iSwitch scheduler relies on the load history record of the previous control period. This record can be implemented using a round-robin database (circular buffer) with constant storage occupation over time. Such round-robin database is easy to reconfigure and manage in most Linux servers with RRDtool [26], which is an industry standard, high performance data logging system.

5.2.Load Power Demand Smoothing

Optimizing the supply-side fluctuation alone cannot achieve significant overhead mitigation (detailed in Section 7.1). To this end, iSwitch leverages the heterogeneity of server clusters to minimize load fluctuation-induced overhead in power management of region III (Section 3).

Figure 10 illustrates the switch management timeline of iSwitch. The controller re-shuffles the renewable energy powered servers at a coarse-grained time interval R (e.g., 15 minutes as the default value in our experiments). During each re-shuffling interval, the average load utilization is recorded in a fine-grained time interval (e.g., 1 minute) and is used to predict the load for the next period. Upon rescheduling, the optimizer in the iSwitch scheduler updates the baseline switch operations of each server cluster in SAB with the goal of mitigating the likelihood of severe load power fluctuation in the next control period. Each switch tuning invoked by CSC will be assigned based on the updated SAB.

At the beginning of each control period, iSwitch recalculates the optimal switch assignment. To simplify the problem, we assume the data center servers are logically divided into c clusters and the load is balanced within each cluster (i.e., almost homogeneous server utilization). Let

denotes the average utilization of each cluster at time stamp i. The utilization history record for the previous control period that consists of m time stamps is: Assuming a total number of N virtual machines is to be connected to the renewable power supply in the next control period. The migration decision for the next control period is

, where k s is the number of VMs selected to be tuned for cluster k. To reduce unnecessary load tuning in the future, we want the aggregate power consumption of the selected VMs to have small oscillations in the next control period. In other words, the standard deviation of the aggregate utilization should be minimized. The aggregate utilization is given by:

1

The standard deviation of the expected utilization in next control period can be calculated as: We solve the above non-linear minimization problem with simulated annealing (SA). Given the utilization history records, our SA solver is capable of finding the desired global extreme very fast. Note that the renewable power supply fluctuation typically occurs on a coarse-grained time interval (several minutes). As a result, the execution time (several seconds in our experiments) of SA solver does not affect the optimization effectiveness. At the beginning of the re-shuffling period, the switching operations are assigned in proportion to the number of servers in the cluster. During the computation, the SA solver iteratively generates a stochastic perturbation for the switching assignment and checks whether or not the optimum solution is reached.

6.Evaluation Methodologies

We evaluate our design with trace-driven simulation. We have developed a framework that simulates dynamic load tuning and hierarchical power control in renewable energy powered data centers. For each scheduled job requests, we calculate its contribution to the overall data center power consumption based on the number of nodes requested and the job's specific resource utilization statistics. Our framework takes realistic wind energy generation traces as supply-side input.

6.1.Data Center Configurations

We assume a raised floor data center consisting of 4,800 servers and the servers are organized as twelve rows with each row powered by a 100KW PDU. There are ten 40U server racks in each row and the server we modeled resembles an HP ProLiant DL 360 G6. The peak and idle power of the modeled server are 186W and 62W respectively. We convert the server utilization traces to its power consumption using the published SPECPower results [27], which have been widely used for data center power evaluation [7,8]. Since the SPECPower results only reflect the server power at intervals of 10% utilization, we use linear interpolation to approximate the power across different load levels.

We evaluate data centers with both homogeneous and heterogeneous load variations. The homogeneous workload configuration assumes that all the servers are running the same workload and have similar utilization levels. As shown in Table 1 , we generate the homogeneous utilization traces from the raw data provided by the Internet Traffic Archive [28]. We convert the request rate (requests per minute) into server utilization by investigating the maximum request rate (corresponding to 100% loading) and minimum request rate (corresponding to 0% loading). The server utilization traces we generated represent a one-week server load variation including idle period, peak hours and daily surge.

Our heterogeneous data center configuration is based on an academic high-performance computing (HPC) center, which hosts more than 600 servers. The HPC center has five major clusters (C-I~C-V) with different service targets and loads, as detailed in Table 2 . Those clusters have 20 to 400 computing nodes and their average utilization ranges from 25% to more than 90%. All the clusters are managed with RRDtool [26], which enables autonomic data logging and trace generation. Since we have limited access to industrial data center traces, we collect real-world workload logs from a well-established online repository [29]. The workload logs provide information such as job arrival times, start time, completion time, size in number of computing nodes, etc. We choose the "cleaned" version of each trace log [30]. These traces have been already scrubbed to remove workload flurries and other anomalous data that could skew the performance evaluation [30].

Table 3 summarizes our evaluated workload trace combinations. We build various workload mixes to mimic today's data centers that are composed of many small co-located clusters. Each workload set in Table 3 consists of five traces [29] which run on the aforementioned five clusters (C-I to C-V) respectively. To form representative workload sets, we characterize workload traces based on their average job size and runtime. In Table 3 , Mix-High includes traces that have larger job size (resulting in >30% average data center utilization) and Mix-Low contains traces that have small job size (resulting in <10% utilization). On the other hand, Mix-Stable consists of five traces that feature relatively longer job runtime and Mix-Bursty consists of traces that have very short job runtime. Low utilization "DAS-fs0" + "DAS2-fs1" + "DAS2-fs2" + "DAS2-fs3" + "DAS2-fs4" Mix-Stable Stable power demand "HPC2N" + "KTH SP2" + "LANL CM5" + "DAS2-fs0" + "SDSC BLUE" Mix-Bursty Bursty power demand "DAS2-fs2" + "DAS2-fs3" + "DAS2-fs4" + "LPC EGEE" + "OSC Cluster" Mix-Rand Random combination "LLNL Thunder" + "OSC Cluster" + "LPC EGEE" + "LANL CM5" + "KTH SP2" Dept-HPC Traces collected from departmental high-performance computing center

6.2.Renewable Energy Supply Traces

We use wind power data traces from The Wind Integration Datasets [31] of the National Renewable Energy Laboratory. These wind generation datasets are time-series data of wind power output derived from commercially prevalent wind turbines characteristics and the manufacturer's rated wind power curve. We carefully selected two groups of traces across different geographic locations and their characteristics are listed in Table 4 .

In Table 4 , capacity factor (CF) is the ratio of the actual wind turbine output to the theoretical peak generations. Since we are interested in the supply variation and intermittency, we have selected a group of traces with various CF values (i.e., Group-I). While a typical capacity factor of wind turbine is 30% [15], higher capacity factor usually represents better wind energy potential, small power variation and less generation stoppage.

The total installed wind turbine capacity in this study equals to the nameplate power of the studied data center. The actual power budget is therefore only affected by the capacity factor. Note that we also evaluate power supply traces of two extreme scenarios (i.e., Group-II): one has very smooth and stable generation and the other has high output fluctuation rate. All the other renewable supply traces can be seen as a combination of the two basic traces plus the intermittently unavailable periods.

7.Experimental Results

This section quantifies the performance and efficiency of iSwitch on a wide range of workload configurations. We first characterize the impact of supply/load power variability on data center load matching using homogeneous workload traces. We then compare the performance overhead and energy utilization of iSwitch to some state-of-the-art approaches. In Table 5 , Utility and Battery are two conventional schemes which do not involve supply-driven load matching. Green is the most sustainable design. Tracking represents emerging design approaches [13,14] which leverage load adaptation to actively track every joule of renewable energy generation.

7.1.Impact of Power Variability

To understand how power variation affects load matching behavior, we monitored the load migration frequency of each VM across different server utilization levels and renewable power supply scenarios. Figure 11 shows the average switching frequency for all VMs for one week's duration. Figure 12 characterizes the standard deviation of the migration activities of a single VM. In Figures 11 and 12 , Idle, Typical and Busy are data center traces that have average utilization levels of 0%, 30% and 60%, respectively. We generate these three synthetic data center traces to mimic low load variation data centers.

High variation load (HVL):

When the supply variation is high (i.e. HVS), heavy switch tuning across a large group of data center servers is common. Therefore, the average switch frequency is high and the standard deviation is not very large. For low supply variation (i.e. LVS), however, the standard deviation increases by 66% since the switching triggered by load oscillations typically stresses a relatively small group of server loads.

Low variation load (LVL):

Since the load variation is less severe, the total switching activities are reduced in both cases (i.e. HVS or LVS) and the average switching frequency is small. For example, Typical has similar loading compared to NASA. However, the former reduces average switching frequency by 31% when the supply variation is high (i.e. HVS) and by 90% when the supply variation is low (i.e. LVS). In Figures 11 and 12 , a combination of LVL and LVS manifests the lowest control effort since the mean value and standard deviation of per VM switching are both small.

To summarize, choosing a subset of server load that has lower total power variation can significantly reduce the load switching demand, especially when the supply variation is low. When the supply variation is high, simply dampening the load power variation has limited impact and in this case switch capping can be used to avoid unnecessary tuning.

7.2.Operational Overhead

Frequent load matching activities result in operational overhead, which is our primary concern in the design of renewable energy powered computing systems. In a virtualized environment, iSwitch could effectively reduce the VM migration rate and help to save data center network bandwidth significantly. The data migration traffic is calculated at rack-level. Each VM live migration transfers approximately the size of the VM's memory between hosts [32]. We assume a VM memory size of 1.7GB in our calculation, which is the default memory size of Amazon EC2 standard instance.

Figure 13 shows the average communication traffic across various workload configurations and wind power supply levels. All the results are normalized to Tracking. We do not show the results of Green because it has the same power tracking frequency as Tracking. As can be seen, on average, iSwitch could reduce 75% of the rack-level traffic and therefore significantly releases the network bandwidth burden. The results are even more impressive for peak traffic hours when the renewable energy fluctuates severely. In Figure 14 we calculate the communication traffic during the top 1% high-traffic hours. Because iSwitch puts a limit on the power tracking activities during fluctuant supply period, it shows only 5% network traffic compared with Tracking.

7.3.Latency per Hour

Another advantage of iSwitch is that it reduces the migration frequency of each VM instance and thereby improves the job turnaround time. Due to the intermittency of renewable generation, stand-alone systems such as Green experience long waiting time (about tens of minutes as observed in our experiments). These systems typically leverage deferrable load [33] to meet the power budget or simply perform load shedding [34] to avoid brownout. Even for utility-connected systems such as iSwitch and Tracking, latency exists due to the data migration time. For example, the time needed for a 1GB VM migration takes about 20 seconds to complete [35].

In this study, we use latency per hour (LPH) to evaluate the performance overhead. For example, a LPH of 10 means each individual VM instance experiences 10 seconds waiting time per hour on average. Figure 15 shows the average LPH across the entire data center servers. The average LPH of iSwitch is about 30 seconds per hour while the average LPH of Tracking reaches 126 seconds per hour. The average LPH of Green, however, is about 1500 seconds per hour -50 times that of iSwitch. Therefore, waiting for renewable energy to resume (e.g. Green) should be the last resort.

7.4.Renewable Energy Utilization

We evaluate the renewable energy utilization (REU) of data centers with different wind power provisioning capacities and workload behaviors. The REU is defined as the amount of wind energy that is actually utilized by the load divided by the total amount of wind energy generation. A higher REU indicates better supply/demand coordination, which reduces on-site energy storage capacity, improves return-on-investment (ROI) and data center sustainability, and eases the initial infrastructure planning.

While iSwitch uses a lazy power tracking scheme, it does not sacrifice energy utilization significantly. As shown in Figure 16 , iSwitch can achieve an average renewable energy utilization of 94%higher than Green (92%) but lower than Tracking (98%). The reason why Tracking outperforms iSwitch on energy utilization is that Tracking tracks every joule of wind energy generation aggressively. Note that a 4% decrease in energy utilization does not mean that iSwitch is less preferable in our study; iSwitch significantly reduces network traffic and improves the performance by 4X. In contrast to Tracking, iSwitch trades off energy utilization for better job turnaround time.

7.5.Optimization Effectiveness

Improperly setting the iSwitch re-shuffling intervals leads to degraded optimization effectiveness. To understand the tradeoff, we characterize the design space by varying the load re-shuffling intervals. In the following discussion, S-x means iSwitch with a re-shuffling interval of x minutes.

We analyze the average network traffic under various re-shuffling intervals. In Figure 17 -a, all the results are normalized to S-15. It shows that increasing the re-shuffling interval could mitigate the overhead and reduce network traffic. For example, S-120 manifests 35% traffic reduction compared with S-15. However, an extended re-shuffling interval could also degrade iSwitch energy utilization due to the decreased adaptivity. We evaluate the impact of long re-shuffling periods on direct renewable energy utilization (DREU), as shown in Figure 17-b . Here, direct renewable energy utilization means the renewable energy directly utilized by the system without passing through batteries. Compared to S-15, S-120 yields about 24% DREU degradation (which means increased battery capacity is required to store the remaining generation). To understand DREU degradation, we show a fraction of data center power consumption trace controlled by S-120, which uses a two-hour load history record as prediction input. In Figure 18 , iSwitch does not react to gradual renewable power supply increase. We recommend a control period of 15~30 minutes. In this case, iSwitch could reduce 75% average load tuning while still maintaining more than 80% direct wind energy utilization (94% overall wind energy utilization if combined with battery). In sum, the length of iSwitch re-shuffling interval affects iSwitch load matching in two ways. First, short re-shuffling intervals limit the load fluctuation mitigation because a short load history record gives less accurate prediction. Second, a shorter time interval means more frequent re-shuffling and therefore magnified overall control overhead. This control overhead arises because the SA solver in iSwitch may request additional switch tuning to mitigate the total variation. For example, instead of directly switching 100 virtual machines from utility to RES, the scheduler may first disconnect 20 high-variation wind-powered VM instances and then connect 120 low-variation VM instances to the wind turbine.

7.6.Total Cost of Ownership

Because iSwitch is capable of utilizing the renewable power directly, we save a large amount of battery capacities. Otherwise, we have to use a large-scale battery to store the unused excess generation, which is not economic and environment-friendly.

In Figure 19 we show the projected annual operating cost of designing a wind energy-powered small-scale data center (i.e. 890KW server deployment). The average retail price of electricity in industrial sector is about $0.07/KW. The estimated energy storage cost is $300/KW for lead-acid batteries [36]. A lower direct renewable energy utilization rate leads to increased battery capacity demand. In Figure 19 , the operating cost of S-120 in the first year is 35% of a utility powered data center (Utility). After three years, the average annual operating cost is only 20% of Utility. The implementation cost is amortized by the renewable energy in the following deployment duration.

8.Related Work

While power-efficient computer architecture is a well studied area in both industry and academia, designing renewable energy powered computing systems gained its popularity only recently [13,14,37,38,39]. In this section we highlight a number of representative works that strive to improve IT efficiency and sustainability in different aspects.

Data center power management: Substantial research has been done on optimizing power efficiency of data centers. At the server level, the most widely used tuning knobs are dynamic voltage and frequency scaling (DVFS), power capping and power state switching [7,40]. At data center level, various mechanisms can be found in recent proposals. For example, some major techniques include virtual machine resource monitoring and capping [23], job scheduling with queueing theory [11], dynamic data channel width adaptation [41], and intelligent server consolidation for co-optimization of cooling and idle power [9,10]. Although all those works can be leveraged to track the time-varying renewable power supply, none of them is aware of the supply variation attributes. As a result, they incur significant power management overhead but gain very limited energy efficiency return.

Emerging green computing techniques: Power intermittency is the most significant challenge in a renewable energy powered computing system. To avoid brownout, recent studies propose load deferment [33] and load shedding [34] to match the demand to the supply. Both approaches are not suitable for data centers which have strict performance requirement specified in the service level agreement (SLA). Although instantaneous performance cannot be guaranteed, one can still use load power adaptation to improve the overall renewable energy utilization and optimize the workload performance with additional power budget [13,14]. Additionally, one can further leverage various renewable energy integration points [39], energy storage elements [42], and distributed UPS system [43] to improve renewable energy utilization. In contrast to existing work, this paper explores the benefits of putting utility power, energy storage, and load migration coordination together. The key novelty of our design is that we propose a supply/load cooperative optimization that significantly reduces existing renewable power management overhead while still maintaining desirable renewable energy utilization.

9.Conclusions

Environmental and energy price concerns have become key drivers in the market for sustainable computing. The advance of renewable energy technologies and continuously decreasing renewable power cost have made renewable energy driven data centers a proven alternative to conventional utility-dependent data centers and the market is rapidly growing.

Matching the variable load power consumption to the intermittent power supply appropriately is the crux of designing a renewable energy powered data center. Conventional workload-driven power management has less adaptivity to the power supply variation while existing Utility Power Cost Stored Enegy Cost power-driven system control schemes are not aware that they are experiencing unnecessary and redundant tuning activities.

As a result, we either miss the opportunity of utilizing precious renewable energy or incur significant load tuning overhead and performance degradation.

In this study, we propose iSwitch, a renewable energy-driven power tuning scheme that addresses a two-fold challenge: the first is to manage intermittent renewable power without sacrificing performance due to power throttling; the second is to ensure high energy utilization with minimized load matching activities. To the best of our knowledge, this is the first paper that digs into renewable power variation characteristics and introduces a supply/load cooperative optimization scheme that minimizes power management overhead. Compared to existing designs, our technique could reduce job waiting time by 80%, mitigate average network traffic by 75%, and rush hour traffic by 95%. Moreover, we can still maintain 96% of the energy efficiency and incur only minor cost increase. This paper shows that we can efficiently handle intermittent renewable power in a lightweight and easy-to-implement manner. We expect that our design will help data center designers take a big step forward in the green computing era.

Acknowledgements

AcknowledgementsThis work is supported in part by NSF grant CSR-1117261, by Microsoft Research Safe and Scalable Multi-core Computing Award, and by NSFC grant 61128004.Chao Li is also supported by a University of Florida Graduate Fellowship.

Failed to load PDF:

StripeM-Inner

Paper sources

Abstract screening pilot

Abstract screening results

Extraction pilot

Extraction results

Research report


Modify setup